|
|
|
Protect Against Electrical Shock Hazards
BY JIM GREGOREC |
In an electrical system, the grounding system is the primary
protection against electrical shock hazards. It provides a low
resistance pathway to ground to protect against electrical faults.
Using proper grounding techniques, testing and maintaining a good
electrical ground, and installing
protection devices are the best ways to protect people and equipment
from electrical shock.
Maintaining a good quality ground starts with wiring the circuit
correctly. The NEC requires that the removal of any device cannot
interrupt the ground path. Receptacle manufacturers have responded
by supplying receptacles with only a single grounding connection.
This would prohibit electricians
from wiring the device in series with the grounding circuit.
Pigtail Connections
A common method of ensuring the ground remains intact is through the
use of a pigtail connection. To make a pigtail connection, take both
ground wires and join them with a six-inch wire of the
same color that has been stripped on either end. Hold all three
tightly and bind them together with a wire connector. Be sure to use
the right size connector for the size and number of wires.
Special connectors are available to make this job easier. With one,
a bare copper wire is inserted through a hole at the top of the
connector. All the wires are then bound together, by twisting the
connector until tight.
Pre-made pigtails are becoming more popular because of the time
saving involved. For example, some connectors now combine a twist-on
wire connector with a pre-crimped pigtail.
The ultra-flexible, six-inch lead provides hassle-free positioning
in a junction box, and the grounding pigtails come with a
pre-crimped fork connection for quick and easy installation of the
device.
Bonding the Junction Box
In many wiring applications, more than one equipment-grounding
conductor enters a junction box. According to section 250-1487 of
the NEC, where more than one equipment-grounding conductor enters a
box, all such conductors shall be spliced or joined within the box
or to the box.
The only exception is for isolated receptacles, covered in section
250-146 (d) where isolated receptacles are required for the
reduction of electrical noise (electromagnetic interference).
For metal junction boxes, the grounding conductors from each device
also needs to be connected to the box with a listed grounding
device, or a grounding screw, that is not used for any other
purpose.
A device may have to be bonded to the junction box with a jumper.
According to section 250-1469 of the NEC, an equipment bonding
jumper shall be used to connect the grounding terminal of a
grounding-type receptacle to a grounded box unless grounded as in
(a) through (d).
(a) A surface mounted box, where the device yoke and the box have
direct metal-to-metal contact. This connection can be used to ground
the device. This provision does not apply to cover mounted
receptacles unless the box and cover combination have been listed as
providing an acceptable ground continuity between the box and
receptacle.
(b) Contact devices or yokes designed and listed for providing the
grounding connection between the device and the junction box. These
shall be permitted in conjunction with the supporting screws to
establish the grounding circuit between the device yoke and
flush-type boxes.
(c) Floor boxes designed for and listed as providing satisfactory
ground continuity between the box and the device.
(d) Isolated receptacles required for the reduction of electrical
noise (electromagnetic interference) on the grounding circuit.
In these applications, the grounding terminal is purposely insulated
form the receptacle mounting to reduce the electrical noise coming
from other loads on the branch circuit.
The receptacle grounding terminal is connected to an insulated
equipment grounding conductor run with the circuit conductors. This
grounding conductor is permitted to pass through one or more
subpanels without connection to the panel board grounding terminal
as permitted in Section 384-2010.
Note that the use of an isolated equipment grounding conductor does
not relieve the requirement for grounding the raceway system and
junction box.
Maintaining a Low Impedance Ground
A good electrical ground is more than following NEC requirements; it
must also be a low impedance system. The ground path is the fault
path for stray current. If electricity follows the path of least
resistance, than the ground circuit must have a lower resistance
than an individual to protect them. The rule of thumb for protecting
people is to maintain a ground impedance of less than one Ohm.
False Grounds
The neutral conductor can only be bonded to the ground conductor at
the main neutral buss, where a large copper conductor carries all
the return and faulted current back to the earth. Sometimes through
error or ignorance, the neutral and ground are connected upstream
from the service entrance.
This is called a false, or bootleg ground. If the neutral and ground
are connected anywhere else in the building, all grounded metal
becomes part of the neutral conductor, constantly energized and
creating various voltage potentials on electronic equipment. When
using common receptacle testers, this condition shows up as normally
wired.
Earth Ground
The pathway to ground extends beyond the main panel to the earth
ground system. The earth ground could be a single ground rod,
multiple ground rods, a mat or a grid system. Section 250-56
addresses the system by stating if the ground electrode is not less
than 25 ohms a second electrode should
be added at least six feet from the first. The grounding system can
be tested with a three-pole earth resistance tester, or a ground
resistance clamp meter.
While testing the resistance of the ground electrode after
installation will satisfy NEC requirements, it is not enough to
ensure protection of personnel or electronic equipment.
The resistance of the ground electrode is heavily dependant on the
soil resistivity. Because soil resistivity relates to the moisture
and temperature, the resistance of the grounding system will vary
throughout the different seasons of the year. To ensure a low
impedance grounding system, include
the ground electrode or earth ground as part of your standard
testing procedures in your facility. A ground resistance clamp meter
enables electricians to measure the resistance of the ground
electrode in a fraction of the time required using the traditional
threepoint fall of potential test.
GFCIs
Electrical code requires the installation of ground fault circuit
interrupters (GFCIs) in residential dwellings to protect against
shock. Receptacles in bathrooms, garages, outdoors, crawl spaces,
unfinished basements, kitchens and near wet bar sinks require
protection.
A GFCI is a receptacle with a built in circuit to detect leakage
current to ground on the load side of the device. When the GFCI
detects leakage current to ground, it will interrupt power to the
load side of the
device, preventing a hazardous ground fault condition.
These devices should be tested regularly, because they rely on
mechanical connections
that will degrade over time. According to a recent study performed
by the Leviton Institute, on average 15 percent of GFCIs were
inoperative when tested.
“Voltage surges from lightning, utility switching and other sources
all take their toll on the devices, which is why Underwriters
Laboratories (UL) requires that GFCIs be tested monthly.”
Equipment Failure
When sensitive electronic equipment fails, the initial reaction is
to throw our hands up and blame it on poor power quality. This makes
the problem seem unmanageable and out of our control. Most of
these problems are actually under our control, because 80 percent of
all power quality problems are found in the electrical distribution
and grounding system.
In addition to preventing the possibility of fire, a good low
impedance electrical system will protect electronic equipment. A
high resistance connection, like a loose wire, will cause the
voltage to fluctuate, or drop, when a large load is applied. If the
voltage drops low enough, it can cause electronic
equipment to lock up, reset or shut down completely.
Grounding is another concern for electronic equipment. While ground
impedance of one Ohm or less may protect people from electric shock,
it may not be adequate protection for electronic equipment. IEEE
recommends a ground impedance to be less than 0.25 Ohms for proper
protection.
Isolated Grounds
In some cases, it is easier to isolate sensitive electronic
equipment than to re-wire an entire circuit. This can be done by
running an isolated ground for the equipment in question, or by
running a new dedicated circuit.
An isolated ground protects the equipment from other equipment on
the same grounding circuit. Electronic equipment can create noise,
which can interfere with the operation of other equipment on the
circuit.
It is important to note than an isolated ground will not protect
equipment from harmonic distortion running through a shared neutral.
In some cases, running a dedicated circuit is necessary to
completely isolate a piece of equipment in order to ensure
protection.
Another article in the code covers the use of transient voltage
surge suppressors. These devices protect power, telephone and cable
lines from transient voltage. Transients are short, high-amplitude
pulses caused by a release of energy onto the electrical system.
These pulses of energy can
be caused by internal sources, such as a capacitor releasing energy
into the system, or external sources like lighting.
The hidden dangers associated with branch circuit wiring are very
serious, but fortunately the precautions are straightforward. We can
protect ourselves and equipment by using certified devices and
testing equipment from reputable manufacturers and implementing
policies on branch circuit
testing. These policies should include verifying proper wiring,
testing devices, checking the integrity of the branch circuit and
measuring the integrity of the grounding system.
Check all devices immediately after installationto verify proper
wiring and test devices. Receptacles should be checked to avoid
common wiring errors, such as reversed polarity or an open neutral.
Checking the voltage level with a voltage tester quickly verifies
that the receptacle has been
correctly wired for either 120 or 220 VAC.
Checking continuity across a switch verifies that it is working
correctly. A variety of testers are available on the market to test
these devices quickly and accurately. In summary branch circuit
testing is an
important part of wiring any circuit. It verifies that devices have
been wired correctly and allows you to protect yourself against the
hidden defects in an electrical system. FSM
Jim Gregorec is a vice-president with IDEAL Industries
Inc., www.idealindustries.com. |
|
|