An “EXIT” is actually made up of
three equally important components:
1. EXIT ACCESS — A clear path
through the building to an EXIT DOOR;
2. EXIT PROPER or EXIT DOOR
leading outside;
3. EXIT DISCHARGE — A safe, clear
path from the exit door to a “public way” such as a street or
parking lot.
NFPA Standard 101, the “Life
Safety Code” sets the actual egress system requirements for any
building.
While the code requirements vary
from occupancy to occupancy, and are beyond the scope of this guide,
a few requirements that are applicable to most public buildings are:
1. All exit access, exit, and
exit discharge must be made up of approved components. Hallways,
aisles, walkways, hinged doors, proper stairs and ramps are approved
components. Ladders, spiral stairways and windows are generally not;
2. The exit access and exit width
are based on the occupant capacity. As a general rule, exit access
should never be narrowed down below the total width of all exit
doors at its end. The exit access and exit doors in any building
must be a minimum of 36” wide;
3. Doors cannot lock against the
direction of exit travel. In occupancies over 50 persons, or high
hazard occupancies such as flammable liquid storage rooms and
electrical load centers, the door must swing in the direction of
exit travel.
In occupancies over 100 persons,
panic hardware is required:
4. Stair treads must be at least
9” deep and risers must not be over 8”;
5. Two exits are generally
required from each area or room, however, minimum dead ends” are
allowed to have only one exit. For typical town office type
buildings, the maximum deadend is 50 feet. For schools, it is 20
feet unless sprinklered, then it is 50 feet. For assembly
occupancies it is 20 feet;
6. EXIT signs are required along
exit access and at exits unless they are “obvious”.
Exit signs must have letters at
least 6 inches tall with 3/4 inch strokes. Some exit signs commonly
available do not meet this requirement. Doors that could be confused
with exits, must be labeled “Not an Exit” or with their purpose such
as” “restroom,” “closet”, etc;
7. Exit signs must be self illuminated or
illuminated by emergency light units. Emergency lighting is required
unless there is no occupancy during dark hours;
8. Self-closing fire doors must never be
blocked open;
9. Exit discharges need proper stairs and must
be kept clear of snow to a public way at all times;
10. Combustible finish in exit access
corridors must not exceed 10 percent. This includes posters and
decorations.
Incipient Suppression
Incipient suppression is often limited to
portable fire extinguishers.
Some buildings have automatic sprinkler
protection and/or automatic suppression systems on special hazards.
A few buildings have wheeled or fixed fire extinguishers or fire
hoses for employee use.
A qualified contractor must maintain sprinkler
and automatic suppression systems annually. Employees who operate
equipment with automatic suppression systems should be trained in
their purpose, automatic activation methods, and how to manually
activate them.
If wheeled/fixed extinguishers or fire hoses
are present, and employees are not specifically prohibited by the
emergency plan from using them, special training should be provided
in their proper operation.
Portable Fire Extinguishers
The proper selection, location, maintenance
and use of portable fire extinguishers can greatly reduce the risk
of a serious injury or a serious property loss in the event of a
fire. As an employer, you have three choices when it comes to
employee use of portable extinguishers:
1. Prohibit their use in the emergency plan.
Require evacuation of all employees immediately. In this case, no
employee training is required;
2. Allow all employees to use extinguishers
and train them annually;
3. Train a selected group of employees
annually (an “incipient fire brigade”), and prohibit their use by
other employees. If employees will be allowed to use extinguishers,
an annual training program must be implemented. As a minimum, this
training should include selection, operation of extinguishers and
the hazards associated with incipient firefighting. Good training
will include the entire Fire Defense Triad and spend a major part
of the training on proper “fight or flee” decision making. While not
specifically required by safety regulations, “hands on” live fire
training greatly increases employee effectiveness if they must ever
use an extinguisher.
It should be considered occasionally, even if
not practical every year.
The selection and placement of extinguishers
is based on the types of fire hazards present in any work area:
• Class A hazards are ordinary combustibles
such as wood, paper, and plastics;
• Class B hazards are flammable/combustible
liquids such as gasoline, fuel oil, solvents, as well as flammable
gases such as LPG and acetylene;
• Class C hazards are any type of fire in the
presence of energized electrical equipment;
• Class D hazards are combustible metals such
as magnesium, titanium and aluminum;
• Class K hazards are commercial cooking
equipment, especially fryers and griddles.
Placement of extinguishers should be as
follows:
• Class A fire hazards (most areas of most
buildings) should be protected by a Class A rated extinguisher
within 75 feet;
• Class B fire hazards should be protected by
a properly sized Class B rated extinguisher within 50 feet;
• Class C rated extinguishers should be
installed in areas where fires involving electrical equipment are
likely or in any area where an untrained member of the public might
grab an extinguisher in an emergency;
• Class D rated extinguishers, approved for
the specific metals present, should be installed where combustible
metals are worked in a manner creating a hazard. In most cases,
this involves handling powdered metals, grinding or machining;
• Class K rated extinguishers should be
installed in or near areas where frying or other cooking with
oils/grease takes place.
The coverage areas for Class A and Class B
extinguishers are circles with the extinguisher in the middle. When
placing extinguishers of any type, look at the area that it will
protect and mount it toward the exit access from that area. All
extinguishers must be mounted using an approved bracket or hanger.
Safety standards require that extinguishers not be mounted higher
than 60 inches.
All extinguishers must be properly maintained
and inspected to ensure proper operation in the event of an
emergency. The requirements are:
• Maintenance — A qualified fire equipment
vendor must conduct annual maintenance of each extinguisher. This
must be documented, usually by attaching a tag.
• Inspection — The employer must conduct monthly visual inspections
(“quick checks”) of all extinguishers in the workplace. This should
be documented
on attached tags or in a log book. A monthly inspection includes
ensuring that the unit is mounted in its place and not blocked; the
gauge (if so equipped) is in the “green,” the pin seal is intact,
and the unit appears overall ready for use.
Types of extinguishers that are available are:
• Pressurized Water — Class A only. These
units come in a standard 21⁄2? gallon size and generate a 25-foot
reach with a water stream that is highly effective at quenching
trash and other ordinary combustible fires. The key disadvantage is
that they are unsafe and potentially lethal around energized
electrical equipment or flammable/combustible liquids.
• Foam — Class A and B. Several different
types of foam are available, with AFFF and FFFP being the most
common. They are effective, in trained hands, at suppressing
flammable/combustible liquid fires, but will not extinguish such
fires if dripping or squirting fuel is present. One big advantage to
this type of extinguisher, however, is that foam can be used to
“secure” gasoline spills and prevent ignition until the fire
department arrives.
Foam conducts electricity so they should not
be used around energized electrical equipment and should never be
provided where the public or untrained staffs have ready access to
them.
• Carbon Dioxide — Class B, C. Carbon dioxide
extinguishers have the shortest range, lowest extinguishing capacity
pound for pound, and require well-trained users to successfully
extinguish a fire with them. They are popular for use around
electrical equipment, though, since they leave no residue and the
gas easily penetrates electrical cabinets and motors.
• Dry Chemical — Class B, C or Class A, B, C
(“Multiple Purpose Dry Chemical”). Pound for pound, these are the
most effective extinguishers for suppressing fires. Since they are
safe for use around energized electrical equipment, multi-purpose
dry chemical extinguishers are recommended in any general hazard
location where the public, tenants, or untrained staff may
misguidedly grab them in an emergency.
• Halon Replacements — Class B, C or Class A,
B, C. Halogenated hydrocarbon, or “halon” fire extinguishers are
still in use in some buildings, with Halon 1211 being the most
common.
These extinguishers are being phased out,
though, due to concerns about damage to the ozone layer.
Several halon replacements are available, at
higher than dry chemical cost, for situations where the powdered
agent from a dry chemical extinguisher might damage sensitive
equipment.
• Class D extinguishers — Also called “dry
powder” extinguishers come in several types for specific types of
metals. Selection of an agent must be based on the metals present
in the work area. FSM /p>
Source:
Maine
Municipal Association Risk Management Service.